A general purpose cement for acid conditions only Resistant to medium concentrations of most of the common organic and inorganic acids except Hydroflouric acid. Recommended where the concentration of the acid is high suitable for high temperature. Unsuited to aqueous solutions, alkaline conditions.
Vicron is used for jointing Acid Resisting brick in construction of vessels in suited for construction of fume chambers and stacks handling hot, dry Acid fumes and vapours.
It is also used for jointing chemical resisting stoneware pipes.
Vicron cement is good bedding material for Acid – Resisting bricks and tiles.
The concrete surface needed protection should be dryed, clean and rough.
The bricks or tiles will be set with Vicron cement over concrete surface applied with a suitable an impermeable interliner.
On the treated surface bricks or tiles are bedded to a thickness of about 6 mm and tamp gently with a wooden piece till the paste squeezes out of joints.
The paste that is squeezed out of the joint should be removed by trowel with good finishing. After the mortar of the joint is dryed treat the joints with 20% Hydrchloric Acid Solution by means of brush. Vicron lining should be always in contact with Acid and not with water.
Concrete substract like Floor, Wall, tanks and similar surface should be protected with a membrane of Bitrok Mastic or compound steel tanks should be protected with rubber or PVC subjected to chemical conditions and temperature of chemical media. The Brick lining is recommended over the protective layer of Bitrok Mastic.
Recomendations :-
Vicron is recommended for chemical plants, Dye intermediates, Steel Industries, Textiles units, Storage Battery Manufacturer, Oil Refinery, Petrochemicals, Fertilizers etc. where acids (except Hydrofloric Acid) such as chronic, Nitric, Hydrochloric Acid, Phosphoric, Sulphuric Acids and dry acids --- and Chimney Lining Work.
Shelf Life : - One year at room temperature from the date of manufacture.
Physical properties of Vicron Mortar and Vicron K which ----I.S. 4832 Part-I -1969 test requirements.
No. | Tests | Tex-Sell Test Result | As per I.S. 4382 Part - I 1969 | |
---|---|---|---|---|
-- | Vicron - K | Vicron | -- | |
01 | Workability at 28°C to 32 °C | 30 to 35 Mins | 30 to 35 Mins | 20 mins |
02 | Compressive strength kgs / cm2 at 7 days. | 200 | 165 | 150 |
03 | Flexual Strength kgs / cm2 at 7 days. | 80 | 60 | 40 |
04 | Bond strength kgs / cm2 at 7 days | 5 | 5 | 5 |
05 | Toluene absorption in percentage at 7 days | 8 to 15 | 8 to 15 | 18 |
When Bedding and Jointing Materials are Different.
Spread the silicate type mortar about 6 to 8 mm thick on the back of the tile or brick. Press the tile on the bed leaving required space for joints between tiles for bricks. After the bedding mortar is set, fill Mp the joints with specified cement.